PowerChute remotely shuts down NetApp storage settings
This environment is stored as NetApp FAS2520 cdot ONTAP 9.1P2
Download the link PowerChute Network Shutdown and double-click to run the installation
Agree to the license agreement as the next step, test JRE. A compatible version will be detected if JRE,PowerChute is installed locally. Do not choose if it is not installed locally, and proceed to the next step.
Enable SNMP support
The function can be turned on as needed, and NetApp can be turned off in this environment. Therefore, this feature is not required
Note that the firewall must be turned off at this time
PowerChute Network Shutdown ports must be opened in the Windows Firewall to enable communication with the Network Management Card (s). Would you like this configuration to be performed automatically?
Select installation path
Installation succeeded
Find the PowerChute shortcut in the start menu and open the
Start initializing links with Smart UPS
Select the corresponding option according to the demand, and there is only one management port in this environment. Select Single
Enter the UPS username and password. Phone defaults to user admin phrase.
Enter the UPS management address for authentication
Confirm configuration for pairing
Waiting for the match to succeed.
Choose to close UPS
End of configuration.
Test the shutdown of the storage and select Runtime exceeded
Set the time and enter the script path
Apply command
Power-off test and observe the UPS log
At this time, PowerChute has started to execute the shutdown script, and this test is successful.